Product

Major Products

Rectifier & DC Power Supply

Plating Rectifiers

Using high-performance IGBT technology, this UPS provides stable output power and precise frequency conversion for a wide range of industrial and testing applications.

Overview

  • We manufacture various industrial rectifiers used in electroplating, electrocoating, anodizing, electrolysis, and general DC power supply systems.

  • The rectifier control methods include IVR input type and thyristor (SCR) control type. Among these, the inductive type supplies excitation voltage to the rectifier transformer using an inductive voltage regulator, allowing tap setting control within the regulation range.

  • The thyristor control method includes two configurations: phase control using thyristors on the AC input side with output voltage adjustment through a transformer, and phase control using thyristors on the transformer secondary side. Products are manufactured and supplied according to customer requirements.

Features

Contactless, Continuous Operation

As a contactless and continuous operation system, it is not affected by failures caused by contact wear or poor electrical contacts.

Built-in Constant Voltage and Constant Current Functions for High Stability

When set to constant voltage or constant current mode, automatic control is applied, providing control stability within ±1.5%.

Improved Maintenance Capability

The unitized design allows maintenance from the front side, significantly improving serviceability.

Enhanced Safety and Reliability

All models are equipped with automatic constant voltage and constant current control functions along with comprehensive protection systems, improving overall operational stability and reliability.

Applications

  • Industrial Rectifier
  • Electroplating Rectifier
  • Electrolysis Rectifier
  • Electrophoretic Deposition (EPD) Rectifier

Transformer Winding

Test Shipment

Electrical Specifications

Category
Category
Characteristics
General
Characteristics
Cooling Method
Natural cooling
General
Characteristics
Duty Rating
100% continuous operation
General
Characteristics
Control Method
SCR phase control method
General
Characteristics
Efficiency
85% or higher
General
Characteristics
Measurement
Conditions
Rated input, float voltage, full load, battery
Input
Phase
3Φ 3W
Input
Rated Voltage
380V AC
Input
Voltage Tolerance
Range
± 10%
Input
Rated Frequency
60Hz ± 5%
Output
Rated Voltage
110V DC
Output
Voltage Stability
± 2%
Output
Rated Current
Capacity
50A
Output
Float Charge
Voltage Range
118V (adjustment range ±5%) at rated input and full load
Output
Equalize Charge
Voltage Range
122V (adjustment range ±5%) at rated input and full load
Output
Ripple
(Ripple Voltage)
3Within 3%
Output
Overload Capacity
120% for 10 minutes
Output
Current Limitation
110% (adjustable from 90% to 125%)
Output
AUTOMATIC
EQUALIZE
CHARGEING MODE
During equalize operation, the system automatically switches to float charge after the preset timer expires.
(Time adjustable)
Overall
Characteristics
Insulation Resistance
Insulation resistance shall be 5 MΩ or higher when measured with a DC 500V insulation tester.
(Excluding control and semiconductor circuits)
Overall
Characteristics
Dielectric Strength
No abnormality shall occur when an AC test voltage of (rated voltage × 2 + 1000V) is applied for 1 minute.
The minimum withstand voltage shall be AC 1500V. (Excluding control and semiconductor circuits)
Overall
Characteristics
Temperature Rise
Under normal operating conditions, temperature rise of each part measured by thermometer method shall be as follows:
– Transformer and reactors: 120°C or lower
– Power semiconductor devices: 80°C or lower
– Capacitors: 75°C or lower

* The enclosure dimensions and weight are based on the rated load capacity and may vary depending on application and operating characteristics.